IS Call Point – Zone 0, 1, 2, 21 & 22 (Ex)

The IS call points offer a solution for Zones 0, 1, 2, 21 & 22 requiring intrinsically safe equipment for the control of fire and gas alarm systems.

Available with and without monitoring resistors the break glass, push button and tool reset versions are certified to ATEX and IECEx standards. The back box can be rotated to give one M20 side entry and dual M20 entries either on the top or bottom.

The IS panel mount indicators and buzzer provide signalling solutions for operator notification from control panels and instrument clusters.

With high ingress protection levels and standard cut out sizes the IS buzzer and LED indicator offer quick instatallation.

Downloads

Beschrijving

The IS call points offer a solution for Zones 0, 1, 2, 21 & 22 requiring intrinsically safe equipment for the control of fire and gas alarm systems.

Available with and without monitoring resistors the break glass, push button and tool reset versions are certified to ATEX and IECEx standards. The back box can be rotated to give one M20 side entry and dual M20 entries either on the top or bottom.

The IS panel mount indicators and buzzer provide signalling solutions for operator notification from control panels and instrument clusters.

With high ingress protection levels and standard cut out sizes the IS buzzer and LED indicator offer quick instatallation.

Beknopte specificaties

  • Material: Corrosion proof, marine grade, copper free LM6 (A413) aluminium.
  • Fixings: Stainless steel.
  • Cable entries: 2 x M20 top/bottom and 1 x M20 left/right. Back box can be rotated to give 2 x bottom and 1 x side entries.
  • Stopping Plugs: 2 x Ex e nylon plugs as standard. Brass and stainless steel plugs optional.

Technische specificaties

  • Ingress Protection
    IP66

Goedgekeurd voor

  • II 1G Ex ia IIC T6 Ga, II 2D Ex t IIIC T60°C Db
  • II 1G Ex ia IIC T4 Ga, II 2D Ex t IIIC T70°C Db

ATEX, IECEx, EAC Ex